Ask what the capacity figure includes.
Nominal energy, documented usable energy and energy already delivered at an AC outlet are different bases. Read the exact documentation and test conditions. A kWh capacity also does not establish the battery or inverter’s kW output limit.
Apply each allowance once.
For an illustrative 5,000 Wh nominal battery: 90% usable share gives 4,500 Wh. Holding 20% of that usable window in reserve leaves 3,600 Wh before conversion. At an assumed 90% inverter efficiency, that supplies 3,240 Wh of AC energy. These percentages are exercise inputs, not defaults for a chemistry or product.
If a source already gives usable battery-side energy, skip the nominal-to-usable reduction. If a figure already measures delivered AC energy, do not subtract an inverter loss a second time. Temperature, standby loads and source test conditions can also matter.
Backup is a system function.
A battery on a product list does not establish outage operation. Controls, inverter capability, circuits and the intended installation must support the use. The runtime tool can calculate energy arithmetic while leaving output capability and compatibility unresolved.
Keep these distinctions.
- Identify nominal, usable and delivered-output figures.
- Keep battery-side and AC-output boundaries visible.
- Capacity is not an output rating or backup approval.
TRY THE REASONING
Practice with visible assumptions.
Answers stay on this page. Check all three exercises to record this lesson as practiced; there is no attempt limit or access gate. Worked answers are available even without JavaScript.
Sources & learning scope
Source concepts reviewed 2026-11-07. Exercise values are explicitly illustrative. This path explains concepts and arithmetic; it is not an installation design or professional certification.
- Australian Government: battery technology
Capacity, usable energy, output and backup configuration only; Australian program and installation rules are not applied here.
- DOE: photovoltaic system design basics
Modules, mounting, inverters and storage are separate system components.